KSA-1200 isolator
The KSA-1200 isolator achieves three terminal isolation of power supply, input, and output. Filter and attenuate on-site current or voltage signals, block ground loops, isolate different ground potentials, suppress the influence of external magnetic fields, and generate standardized analog signals.
1、 Main technical parameters
Number of channels
model | number of channels | model | number of channels |
KSA-1211 | One in, one out | KSA-1251 | Two in two out (with HART) |
KSA-1231 | One in one out (with HART) | KSA-1261 | One in, three out |
KSA-1212 | One in, two out | KSA-1271 | One in, four out |
KSA-1221 | Two in, two out | KSA-1281 | Two in and four out |
KSA-1241 | One in two out (with HART) |
power supply
20-32Vdc, voltage ripple Vpp ≤ 5V (pp)
Power consumption: When powered by 24V, full load<1W
Transient overvoltage at power port: ± 120V DC/10s
Power port overcurrent limit<300mA
Special specifications can provide 220Vac voltage supply
Input signal
Two wire signal, three wire signal, four wire signal (active signal)
Current: overcurrent limit protection of about 30mA
Voltage: Overvoltage limit protection of approximately ± 60V DC/10s
Output signals 0-20mA, 4-20mA, 0-5V, 0-10V, 1-5V, 2-10V, passive output (Sink mode)
Output accuracy 0.05% F.S
Temperature drift 0.002% F.S/℃
Continuous working temperature -20~+60 ℃
Dimensions 17.8 × 110 × 119mm (width × height × depth)
Safety IEC61010-1, input, output, power supply three terminal isolation, dielectric strength 2500Vrms, 10 second dielectric withstand voltage test. Insulation resistance:>100M Ω between input/output/power supply