Welcome to visit Kunshan Haien Electrical Co.,Ltd. Official website! Site Map | 
Kunshan Haien Electrical Co.,Ltd.

Engaged in industries such as electrical instruments, oil stations, etc

Hotline0512-57787475-800
Modular instrument
KSA-1200 isolator

KSA-1200 isolator

The KSA-1200 isolator achieves three terminal isolation of power supply, input, and output. Filter and attenuate on-site current or voltage signals, block ground loops, isolate different ground potentials, suppress the influence of external magnetic fields, and generate standardized analog signals.

OnlineHotline
0512-57787475-800

KSA-1200 isolator

The KSA-1200 isolator achieves three terminal isolation of power supply, input, and output. Filter and attenuate on-site current or voltage signals, block ground loops, isolate different ground potentials, suppress the influence of external magnetic fields, and generate standardized analog signals.

1、 Main technical parameters

Number of channels

model

number of channels

model

number of channels

KSA-1211

One in, one out

KSA-1251

Two in two out (with HART)

KSA-1231

One in one out (with HART)

KSA-1261

One in, three out

KSA-1212

One in, two out

KSA-1271

One in, four out

KSA-1221

Two in, two out

KSA-1281

Two in and four out

KSA-1241

One in two out (with HART)


 

power supply

20-32Vdc, voltage ripple Vpp ≤ 5V (pp)

Power consumption: When powered by 24V, full load<1W

Transient overvoltage at power port: ± 120V DC/10s

Power port overcurrent limit<300mA

Special specifications can provide 220Vac voltage supply

Input signal

Two wire signal, three wire signal, four wire signal (active signal)

Current: overcurrent limit protection of about 30mA

Voltage: Overvoltage limit protection of approximately ± 60V DC/10s

Output signals 0-20mA, 4-20mA, 0-5V, 0-10V, 1-5V, 2-10V, passive output (Sink mode)

Output accuracy 0.05% F.S

Temperature drift 0.002% F.S/℃

Continuous working temperature -20~+60 ℃

Dimensions 17.8 × 110 × 119mm (width × height × depth)

Safety IEC61010-1, input, output, power supply three terminal isolation, dielectric strength 2500Vrms, 10 second dielectric withstand voltage test. Insulation resistance:>100M Ω between input/output/power supply


Tags: All